- 1000V
n4000MΩ
- 1000V
-
- 500V
n4000MΩ
- 500V
-
- 250V
n4000MΩ- Hot-line state(30V minimum) detection
- 250V
-
- Large volt mark with the buzzer sound
-
- Automatic data hold function
-
- Bar graph just like analog meter
-
- Large display with backlight
-
- Easy to use & tough body
-
- IP54
-
- Continuity test(200mA) function
Specifications
Function | Measuring range | Best accuracy | Resolution |
---|---|---|---|
MΩ | 4M/40M/400M/4000MΩ | ±(3%+4) | 0.001MΩ |
Rated voltage | 250/500/1000V | ||
ACV/DCV | 600V(AC/DC Automatic detection) | ±(3%+2) | 1V |
Ω(Continuity) | 4000Ω(Buzzer and ALARM indicator) | ±(3%+3) | 1Ω |
Ω | 40Ω | ±(3%+10) | 0.01Ω |
Rated current | 1.0~1.2mA |
Short-circuit current | 2mA or less |
Live circuit detection | At 30V AC/DC or more, inhibits test, buzzer sounds and ALARM indicator lights up |
Battery | LR6(AA alkaline battery)1.5V×6 |
Size/Mass | H170×W142×D57mm/Approx. 600g |
Safety standard | IEC61010 CAT.Ⅲ 600V |